Topics in this sectionInstalling AC machines4 topics
- Installing transformers
- Installing induction motors
- Installing synchronous motors
- Installing generators
A synchronous motor is an AC motor that runs at a constant speed determined by the frequency of the supply current, regardless of the load. In this learning activity, you will learn how to define, identify types of, and install synchronous motors using proper safety procedures and tools.
A synchronous motor is an AC motor that operates at a constant speed (synchronous speed) when connected to a three-phase supply. Unlike induction motors, synchronous motors can operate at constant speed regardless of load changes, making them ideal for applications requiring precise speed control.
The synchronous speed (Ns) is calculated using the formula:
Ns=P120×f
Where:
- Ns = synchronous speed in revolutions per minute (rpm)
- f = supply frequency in Hertz (Hz) — Tanzania uses 50 Hz
- P = number of poles in the motor
For example, a synchronous motor with 4 poles connected to a 50 Hz supply in Tanzania has a synchronous speed of:
Ns=4120×50=1500 rpm
During practical work, you should be able to identify these main types:
-
Salient Pole Motors — Have projecting poles visible on the rotor surface. Used where low speed is required (e.g., large hydro generators). They are easier to manufacture for motors with many poles.
-
Non-Salient (Cylindrical) Motors — Have a smooth cylindrical rotor. Used for high-speed applications (e.g., 1500 rpm and above). They operate more quietly and are mechanically stronger.
-
Three-Phase Synchronous Motors — Most common type in industrial applications. They require a three-phase AC supply and a DC supply for the rotor field.
-
Single-Phase Synchronous Motors — Used in timing devices and clocks where constant speed is essential.
Before installation, ensure you have:
- Safety goggles, overalls, and safety boots
- Insulated gloves
- Megger, multimeter, installation tester, and clamp on meter
- Screwdrivers, spanners, combination pliers, and diagonal cutters
- Electrician's knife, Rawl plugs, ball peen hammer, and cross peen hammer
Safety precautions:
- Always disconnect the power supply before working on any motor
- Verify power is off using a multimeter or voltage tester
- Ensure the motor is properly grounded
- Wear appropriate PPE at all times
- Never work on live equipment
Follow these steps when installing a synchronous motor:
1. Site Selection and Foundation Preparation
- Choose a dry, well-ventilated location free from dust and corrosive gases
- Ensure the foundation is level and strong enough to support the motor
- Use Rawl plugs and appropriate fixings to secure the motor base
2. Mounting the Motor
- Position the motor on the foundation
- Use a spirit level to ensure it is perfectly horizontal
- Secure with anchor bolts through the mounting holes
- Check alignment with the driven equipment (pump, compressor, etc.)
3. Electrical Connections
- Connect the three-phase supply cables to the motor terminals
- Ensure correct phase sequence (L1, L2, L3)
- Connect the DC field winding to the excitation supply
- Ensure proper grounding of the motor frame
4. Coupling and Mechanical Connection
- Connect the motor shaft to the driven equipment using appropriate coupling
- Check alignment and adjust if necessary
- Ensure the coupling is properly aligned to prevent excessive vibration
After installation, perform these tests before energizing:
- Continuity Test — Use a multimeter to check all windings for continuity
- Insulation Resistance Test — Use a megger to test insulation resistance between windings and between windings and earth. Minimum acceptable value is 1 MΩ
- Earth Continuity Test — Verify the motor frame is properly grounded
- Voltage Test — Confirm correct voltage at the motor terminals
- Rotation Test — Briefly energize the motor to verify correct rotation direction
In Tanzania, synchronous motors are commonly used in large water pumps at municipal water supply stations in cities like Dar es Salaam and Arusha, where constant speed is essential for reliable water delivery. A technician working at such a facility would need to install and maintain these motors to ensure uninterrupted water supply to the community.
How you'll be assessedProcess assessment · Outcome assessment · Knowledge assessment
Process assessment
The student should be able to:
- Interpret the drawing.
- Identify tools, equipment and required materials.
- Fix and align AC machines on its bed.
- Make visual inspection of broken dial faces on the machines.
- Make earth continuity test and insulation test between phase and earth and between phase and phase.
- Identify phase marking.
- Carry out testing of AC machine.
- Apply safety precautions.
- Clean the work area.
Outcome assessment
A synchronous motor placed on its bed safely and supply conductors bunched neatly. Connections are made as per manufacturer’s manual. A.C. machine operates as per manual instructions.
Knowledge assessment
Knowledge evidence:
Detailed knowledge of:
Method used: The should explain how to install synchronous motors.
Principles: The student should explain the principles of installing synchronous motors.
Theories: The student should explain:
- Application of synchronous motors.
Detailed knowledge about:
- Safety precautions, testing procedures, and I.E.E. regulations.
- Hazards classification and control Maintenance of machines
Question
What is the synchronous speed of a 4-pole synchronous motor when connected to a 50 Hz supply in Tanzania?
Sign in to submit your answer and have it count toward your mastery.
Sign in to practiceTutor
Stuck? Ask me anything about this topic.
Sign in to ask the Sonza AI Tutor about this question.
Sign in to askDiscussions
No questions yet