A parallel clamp joint is a cold electrical joint in which two conductors are laid side by side and gripped together by a metal clamp that is tightened with bolts or screws. No heat or solder is used. The pressure of the clamp holds the conductors firmly and lets current pass from one to the other.
The most common parallel clamp is the parallel groove clamp. It has a metal body with two grooves, a top plate and one or more bolts. One conductor lies in each groove, and tightening the bolts squeezes both conductors between the body and the plate.
Parallel clamp joints are used to:
- Connect a branch (tap-off) conductor to a main conductor without cutting the main, for example where the service line to a house leaves an overhead line
- Connect the jumper that carries current past the insulators at an angle pole or end pole of an overhead line
- Join earthing conductors
You can see these clamps on the overhead lines of the power utility. Look at them from the ground only. Never climb a pole or go near a line.
| Type | Where it is used |
|---|---|
| Aluminium clamp | Joining aluminium conductors to each other |
| Copper or brass clamp | Joining copper conductors to each other |
| Bimetallic clamp | Joining an aluminium conductor to a copper conductor; it prevents the corrosion that happens when the two metals touch directly |
| One-bolt, two-bolt and three-bolt clamps | More bolts are used for larger conductors and higher currents |
| Equal-groove and unequal-groove clamps | Equal grooves for two conductors of the same size; unequal grooves for a large main and a smaller branch |
For insulated overhead cables there are also insulation-piercing connectors. Their teeth bite through the insulation when the bolt is tightened, so the cable is not stripped.
- Combination pliers and long nose pliers
- Electrician knife
- Measuring tape
- Spanner or screwdriver that fits the clamp bolts
- Wire brush or abrasive cloth
- Multimeter
- Parallel clamp of the correct size and material
- Two conductors
- Safety goggles, safety boots and overalls
- Workbench
- Make sure the conductors are dead. In the workshop, use lengths of cable that are not connected to any supply. On a real installation the circuit must be switched off, locked off and proved dead with a voltage tester before it is touched. Joints on overhead lines are made only by authorised utility staff.
- Select the clamp. Its material must suit the conductors, and its grooves must fit their sizes.
- Measure and mark. Measure the length of the clamp. If the conductors are insulated, mark a length equal to the clamp plus about 10 mm at each side.
- Strip the insulation. Pare the insulation away with the electrician knife as if sharpening a pencil, cutting away from your body. Do not cut straight round the cable, because this nicks the strands.
- Clean the conductors. Brush the bare metal until it is bright. Aluminium forms an oxide film within minutes, so coat it with jointing compound straight after brushing.
- Assemble the joint. Loosen the bolts and lay one conductor in each groove, so that the two lie parallel and fully seated with about 10 mm showing at each side of the clamp.
- Tighten the bolts. Tighten them a little at a time, one after the other, so that the plate comes down evenly. Tighten firmly, but do not force the bolts; too much force crushes the strands or strips the thread.
- Insulate the joint if needed. Where the conductors are insulated, wrap the joint with PVC insulation tape in at least two layers, each turn overlapping half of the one before, and continue about 25 mm onto the insulation at each side. Some clamps are supplied with a cover to fit instead.
- Look: both conductors are fully in their grooves, no strands are outside the clamp, and the plate sits level.
- Pull: tug each conductor firmly. Neither should move.
- Measure: with the joint dead, set the multimeter to its lowest resistance range and measure from one conductor to the other across the joint. The reading should be close to zero.
The clamp works by pressure. The harder and more evenly the clean metal surfaces are pressed together, the lower the resistance of the joint. The heat produced in a joint is P = I² × R.
- A good joint of 0.01 Ω carrying 20 A produces 20 × 20 × 0.01 = 4 W.
- A loose joint of 0.5 Ω carrying the same 20 A produces 20 × 20 × 0.5 = 200 W, enough to burn the insulation and start a fire.
Conductor materials. Copper is a very good conductor, is ductile and resists corrosion. Aluminium is lighter and cheaper, which is why it is used for overhead lines, but it conducts less well, is softer and forms an oxide film.
What makes the joint strong: clean conductors, the correct size and material of clamp, a large contact area, bolts tightened evenly, undamaged strands and no strain on the joint.
Advantages: the joint needs no heat, is quick to make, can be undone and re-used, and allows a branch to be taken without cutting the main conductor.
Choosing this joint: use a parallel clamp for large bare or stranded conductors, for tap-offs and for outdoor work. For small cables inside buildings, use terminal blocks, crimp connectors or the terminals of accessories instead.
A student joins two 16 mm² stranded copper conductors with a two-bolt copper clamp that is 40 mm long.
- Stripped length on each conductor: 40 mm + 10 mm + 10 mm = 60 mm.
- The student pares 60 mm of insulation off each conductor, brushes the strands bright and lays one conductor in each groove.
- The bolts are tightened evenly with a spanner.
- Both conductors pass the pull test, and the multimeter shows a reading close to 0 Ω across the joint.
- The joint is wrapped with two half-overlapped layers of PVC tape.
- Never make or test a joint on a live conductor.
- Wear safety goggles when cutting, stripping and brushing, and keep your fingers behind the knife blade.
- Keep the bench clear so that tools do not fall on your feet.
- Put insulation strippings and wire offcuts in the waste bin; copper and aluminium offcuts can be kept for recycling.
- Wipe the tools, close or sheath the knife, switch off the multimeter, and return the tools, clamps and unused cable to the store.
In a town such as Morogoro, the low-voltage overhead line along a street supplies many houses. At the pole nearest each house, the service line is connected to the main line with parallel clamps, so the main conductor is never cut. Only trained and authorised utility technicians do this work. An electrician inside a building uses the same idea, clean metal held under firm pressure, every time a terminal screw is tightened.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Identify tools, equipment, and materials required.
- Prepare cables for termination.
- Make cable joints.
- Test joints.
- Apply safety precautions.
- Clean work area.
- Store tools, equipment, and remaining materials.
Tathmini ya matokeo
The parallel clamp joint made is mechanically and electrically sound.
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
- Types of parallel clamp joint.
Method used: The student should explain how to:
- Prepare cables for jointing.
- Execute particular joints.
Principles: The student should explain the principles of making parallel clamp joint.
Theories: The student should explain:
- Properties of conductor materials.
- Factors determining strength of various joints.
- Advantages of joints.
- How to select the correct type of joint for a particular application?
Circumstantial knowledge:
Detailed knowledge about:
- Safety measures involved in making joints.