Mada za sehemu hiiInstalling cablesMada 4
- Installing PVC cable
- Installing paper insulated cable
- Installing armoured cable
- Performing underground wiring systems
Installing Armoured Cable
An armoured cable is a type of electrical cable that has an additional protective layer made of steel or aluminium. This extra layer provides strong protection against physical damage, making the cable suitable for harsh environments where mechanical stress, moisture, or impact could occur. The armour layer also helps to ground the cable when properly connected, adding an important safety feature to the electrical installation.
An armoured cable consists of five main parts:
-
Conductors — These are the metal cores (usually copper or aluminium) that carry electrical current. They provide a low-resistance path for electricity to flow.
-
Insulation — This is a protective layer around each conductor that prevents current leakage and ensures safe delivery of electrical energy. Common insulation materials include PVC and XLPE.
-
Bedding (inner sheath) — This layer sits over the insulation to protect the cable from moisture, gases, and harmful liquids. It is usually made of rubber or PVC.
-
Armouring — This is the steel or aluminium layer that provides mechanical protection against damage during installation and handling. It is the key feature that distinguishes armoured cables from unarmoured cables.
-
Outer sheath — This is the final protective layer that covers the armouring and protects it from atmospheric conditions like sunlight, rain, and chemicals.
Armoured cables are classified based on the material and form of their protective layer:
Steel Wire Armoured Cable (SWA)
This is the most common type of armoured cable. The armour is made from steel wires wound helically around the cable. SWA cables have high tensile strength and can withstand significant mechanical stress. They are suitable for direct burial underground and for installations where the cable may be exposed to heavy loads.
Steel Tape Armoured Cable (STA)
In this type, the armour consists of steel tapes wound around the cable. STA cables provide good protection against crushing, making them suitable for direct burial in areas where the cable may be subjected to pressure, such as under roads or pathways.
Aluminium Wire Armoured Cable (AWA)
This type uses aluminium wires for the armour layer. AWA cables are primarily used for single-core cables because aluminium is non-magnetic, which prevents overheating problems that would occur with steel armour in single-phase applications. They are lighter than steel-armoured cables.
Armoured cables are used in environments where cables face risk of physical damage:
- Construction sites — Where cables may be damaged by machinery or construction activities
- Industrial settings — Such as factories and manufacturing plants with heavy equipment
- Underground installations — Including direct burial in soil
- Outdoor installations — Where cables are exposed to weather conditions
- Mining sites — Where cables must withstand harsh conditions
Advantages
- High resistance to mechanical damage and stress
- Longer lifespan compared to unarmoured cables
- Suitable for direct burial without additional protection
- Reduced maintenance requirements
- Can provide earth continuity when properly connected
- Good resistance to moisture and chemicals
Disadvantages
- More expensive than unarmoured cables
- Less flexible, making installation more difficult
- Heavier and harder to handle
- Requires special tools and techniques for termination
Before installing armoured cables, ensure the following tools and equipment are available:
Tools:
- Electrician's tool kit
- Combination pliers
- Electrician's knife
- Measuring tape
- Claw hammer
- Set of screwdrivers
- Cable pulling socks
Safety Gear:
- Leather gloves
- Overalls
- Safety boots
- Safety goggles
Follow these steps to install an armoured cable correctly:
-
Plan the cable route — Study the wiring diagram to understand the cable path, connection points, and required cable size. Check for obstacles, safety hazards, or other services like water pipes and gas lines.
-
Select appropriate tools and materials — Choose the correct type and size of armoured cable for the installation. Ensure all tools are in good condition.
-
Wear appropriate PPE — Put on safety boots, gloves, overalls, and safety goggles before starting work.
-
Measure and cut the cable — Measure the required length and cut the cable to size using appropriate cutting tools. Ensure the cut is clean and square.
-
Prepare the cable ends — Strip back the outer sheath carefully using an electrician's knife. Remove the armouring and bedding to expose the conductors and insulation. Take care not to damage the insulation.
-
Terminate the cable — Use appropriate termination kits to connect the cable to the intended points. Ensure all connections are tight and secure to prevent faults or overheating.
-
Support the cable — Install proper supports, clips, or clamps along the cable route to keep the cable secure. Follow the manufacturer's instructions regarding minimum bending radius.
-
Test the installation — Perform continuity and insulation resistance tests to verify the cable is correctly installed and safe to energize.
-
Clean and store — Clean the working area and return all tools to their storage location.
- Always switch off power and lock it out before installation
- Wear appropriate PPE at all times
- Inspect the site for hazards such as flammable materials
- Keep cables away from other services like communication lines and water pipes
- Follow the manufacturer's instructions for bending radius
- Label cables clearly for identification
- Conduct visual inspection before restoring power
- Refer to relevant standards and regulations
Problem: A construction site in Dar es Salaam requires an armoured cable to supply power to a temporary site office 30 metres from the main distribution board. The load current is 25 A. The electrician needs to select an appropriate armoured cable.
Solution:
Step 1: Determine the load current (already given): I=25A
Step 2: Refer to standard cable selection tables (BS 7671). For a 25 A load with armoured cable installed in a conduit underground, a 4 mm² copper conductor would typically be suitable.
Step 3: Since the cable is for outdoor/construction site use and may be exposed to mechanical damage, select a Steel Wire Armoured (SWA) cable for extra protection.
Selected cable: 4 mm² 3-core SWA cable (for three-phase supply) or 2.5 mm² 2-core SWA cable (for single-phase), depending on the system design.
In Tanzania, armoured cables are commonly used for wiring markets such as Kariakoo in Dar es Salaam or Mwanza's Nyerere Road market, where shop owners need reliable and safe electrical connections that can withstand the busy, sometimes harsh environment. A small restaurant owner in Arusha might use armoured cable to run power from the main supply to their outdoor seating area, ensuring the wiring is protected from accidental damage caused by customers moving furniture or foot traffic.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Select tools, equipment and safety gears
- Interpret wiring drawings
- Select area for cable installation
- Lay /mount the Armoured Cable and support it.
- Terminate the Armoured Cable with appropriate termination kit.
- Perform testing of cable.
- Observe safety precautions.
- Clean the work area. Store tools, equipment and safety gears.
Tathmini ya matokeo
The installation of amoured cables was performed as per procedures prescribed by the I.E.E. regulations.
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to install Armoured Cable.
Principles: The student should explain the principles related installing Armoured Cable.
Theories: The student should explain:
- The types of Armoured Cable Cables and application.
- Application of Armoured Cable.
- Theory of estimating cable size.
- Type of material for manufacturing of cables.
Detailed knowledge about:
- Safety measures to be observed while installing cables.
- IEE Regulations to cable installation.
Swali
Which of the following lists the five main components of an armoured cable in the correct order, from the innermost layer to the outermost layer?