Mada za sehemu hiiInstalling three-phase switch gearsMada 5
- Installing three-phase distribution board
- Installing three-phase isolator
- Installing a three-phase switch fuse
- Installing change-over switch
- Installing power factor correction facility
Power Factor Correction Facility
Power factor (PF) is the ratio of real power (measured in kilowatts, kW) to apparent power (measured in kilovolt-amperes, kVA). It shows how efficiently electrical power is being used in an alternating current (AC) system.
PF=Apparent Power (kVA)Real Power (kW)=cosϕ
Where φ (phi) is the phase angle between voltage and current. A power factor of 1.0 (or 100%) means all power is being used effectively, while a lower power factor indicates inefficiency.
When power factor is low (typically below 0.85), the electrical system must carry more current than necessary to deliver the same amount of useful power. This causes several problems:
- Higher electricity bills: TANESCO charges penalties for low power factor because the distribution company must supply more current than needed
- Increased losses: More current flowing through wires causes greater heat losses (I2R losses)
- Overloaded equipment: Cables, transformers, and switchgear must be oversized to handle the extra current
- Voltage drop: Low power factor causes larger voltage drops along distribution lines
A Power Factor Correction (PFC) Facility is a system that improves the power factor of an electrical installation by adding capacitors (capacitor banks) to the circuit. Capacitors provide reactive power (VARs) that cancels out the reactive power drawn by inductive loads like motors, fluorescent lights, and transformers.
The capacitor bank is typically installed:
- Near the main distribution board
- At the point of common coupling
- Or at individual load locations for large inductive equipment
A typical PFC installation includes:
- Capacitor banks: Multiple capacitors connected in a bank to provide the required reactive power compensation
- Three-phase isolator: To safely disconnect the capacitor bank for maintenance (this is the "three-isolator" mentioned in the procedures)
- Switch fuse unit: To protect the capacitor circuit from overcurrent
- Control relay: Automatically switches capacitor stages in and out based on the measured power factor
- Power factor meter: Displays the current power factor
- Enclosure: Protective housing for all components
Step 1: Planning and Preparation
- Study the electrical load to determine the required capacitor size (measured in kVAR)
- Select appropriate components with correct voltage and current ratings
- Ensure the location is accessible, dry, and well-ventilated
- Gather all tools and materials needed
Step 2: Safety Precautions
- Switch OFF the main power supply
- Use a voltage tester to confirm the circuit is de-energized
- Wear appropriate PPE: safety goggles, overalls, safety boots
- Use insulated tools
- Follow lockout/tag-out procedures
Step 3: Mounting the Components
- Mount the capacitor bank enclosure securely to the wall or installation board
- Install the three-phase isolator in an accessible location
- Mount the switch fuse unit
- Ensure all components are level and properly aligned
Step 4: Wiring the PFC Facility
- Connect the three-phase supply to the isolator
- Connect the isolator to the switch fuse unit
- Connect the switch fuse to the capacitor bank
- Ensure correct phase connections (L1, L2, L3)
- Connect the neutral and earth wires properly
- Label all wires after connection
Step 5: Testing and Commissioning
- Have the teacher inspect all connections before powering
- Switch ON the power and observe the power factor meter
- Verify that the power factor improves to near unity (0.95–1.0)
- Check that capacitors switch in automatically as loads change
- Test the isolator to ensure it safely disconnects the capacitor bank
A small factory in Arusha has a measured apparent power of 100 kVA and real power of 60 kW. Calculate the current power factor and determine the capacitor size needed to improve it to 0.95.
Step 1: Calculate current power factor
PFcurrent=10060=0.60
Step 2: Find the reactive power
Qinitial=S2−P2=1002−602=10000−3600=6400=80 kVAR
Step 3: Find target apparent power at PF = 0.95
Starget=PFP=0.9560=63.16 kVA
Step 4: Find target reactive power
Qtarget=Starget2−P2=63.162−602=3989−3600=389=19.7 kVAR
Step 5: Calculate capacitor size needed
Qcapacitor=Qinitial−Qtarget=80−19.7=60.3 kVAR
Therefore, a capacitor bank of approximately 60 kVAR should be installed.
- Always de-energize the circuit before working
- Use insulated tools and wear proper PPE
- Ensure the capacitor bank is discharged before touching terminals (capacitors can retain dangerous charges)
- Follow manufacturer's instructions for all equipment
- Keep the work area dry and clear of obstructions
- Verify all connections are tight to prevent overheating
After installation:
- Visual inspection of all connections
- Verify phase sequence is correct
- Test isolator operation under no-load conditions
- Check power factor improvement with a meter
- Document the installation for future maintenance
In Tanzania, many small businesses and workshops using three-phase equipment (like welding machines, compressors, and woodwork machines) experience low power factor due to the inductive nature of these loads. A local welding workshop in Mwanza that installs a power factor correction facility can reduce their monthly electricity bill by up to 15–20%, as TANESCO charges lower demand charges when the power factor is maintained above 0.90. This also prevents premature failure of motors and reduces the need for oversized generators during power outages.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Interpret single line and lay out drawings.
- Select tools, equipment and safety gear.
- Select the correct sizes of cables as indicated by drawings.
- Connect final circuits to switch gears.
- Perform necessary tests.
- Observe safety.
Tathmini ya matokeo
Power factor correction facility installed as per technical specifications and I.E.E. regulations.
Tathmini ya maarifa
Methods used: The student should explain how to Install Power Factor Correction Facility.
Principles: The student should explain the principles related to installing Power Factor Correction Facility.
Theories: The student should explain:
- Power Factor Correction Facility
- Types of Power Factor Correction Facility.
Detailed knowledge about:
- Workplace accidents and incidents
Swali
What is the definition of power factor in an AC electrical system?
Ingia ili kuwasilisha jibu lako na lihesabiwe katika umahiri wako.
Ingia ili kufanya mazoeziMwalimu
Umekwama? Niulize chochote kuhusu mada hii.
Ingia ili kumuuliza Mwalimu wa AI wa Sonza kuhusu swali hili.
Ingia ili kuulizaMajadiliano
Hakuna maswali bado