Mada za sehemu hiiInstalling control of AC machinesMada 6
Installing DOL Starter by Using Jogging Method
The jogging method (also called inching) is a technique used to start and stop a motor momentarily for short periods — just enough to position, align, or operate equipment intermittently. When you press the jog button, the motor runs only while you hold it down; as soon as you release it, the motor stops immediately.
This is different from a normal Start button, which uses an auxiliary contact to keep the motor running even after you release the button.
Jogging is commonly used in:
- Conveyors — to move materials short distances
- Cranes and hoists — for precise lifting and positioning
- Machine tools — for fine adjustments
- Air conditioning compressors — during installation testing or maintenance
The jogging method ensures the motor receives the correct voltage and current, prevents damage from prolonged starts, and reduces safety risks during intermittent operations.
Before starting, gather these tools and components:
- Screwdrivers (flat and Phillips)
- Wire strippers and cutters
- Crimping tool
- Pliers (combination and diagonal cutting)
- Multimeter or clamp meter
- Insulation resistance tester
- Drill and drill bits
- Allen keys
- Contactor (magnetic switch)
- Thermal overload relay
- Circuit breaker (MCB or MCCB)
- Normally Open (NO) Start button
- Normally Closed (NC) Stop button
- Jog button (NO, momentary)
- Electrical wires (appropriate gauge)
- Cable lugs, glands, and conduits
- Junction box or control panel enclosure
- Terminal blocks
- Electrical tape and heat-shrink tubing
- Labelling tags and markers
- Personal Protective Equipment (PPE): safety boots, goggles, gloves, and overalls
Follow these steps carefully:
Step 1: Verify Motor Specifications
Check the motor's nameplate for voltage, phase (single or three-phase), power rating, and wiring configuration. Ensure the DOL starter components match the motor requirements.
Step 2: Disconnect Power Supply
Before any electrical work, isolate the power supply. Lock out and tag out the circuit to prevent accidental re-energizing.
Step 3: Install the Circuit Breaker
Mount an MCB or MCCB to protect the circuit against overcurrent. Connect the three-phase power supply (L1, L2, and L3) to the input terminals of the circuit breaker.
Step 4: Connect Power to Contactor
From the circuit breaker output terminals, wire the phases to the contactor input terminals (L1, L2, and L3).
Step 5: Connect Contactor to Motor
Wire the contactor output terminals (T1, T2, and T3) to the motor terminals (U, V, and W).
Step 6: Install Thermal Overload Relay
Connect the thermal overload relay between the contactor and the motor. This protects the motor from overheating due to overload or jammed machinery.
Step 7: Wire the Start and Stop Buttons
- Wire the Normally Open (NO) Start button in parallel with the remote control module (if used).
- Wire the Normally Closed (NC) Stop button in series with the control circuit.
Step 8: Connect Contactor Coil
Connect the contactor coil terminals (A1 and A2) to the push buttons to control the contactor activation. Connect A2 to the neutral wire.
Step 9: Wire the Auxiliary Contact
Connect an auxiliary Normally Open (NO) contact of the contactor across the Start button. This holds the contactor energized after the Start button is released, keeping the motor running.
Step 10: Wire the Jog Button (Key Step)
This is the most important difference from a regular DOL starter:
Connect the Jog button (NO) in parallel with the Start button, but do NOT connect it to the auxiliary NO contact.
This arrangement ensures that:
- When you press Start, the auxiliary contact keeps the contactor energized → motor runs continuously
- When you press Jog, the contactor is energized only while the button is pressed → motor stops immediately when released
Suppose you are installing a DOL starter with jogging for a small air conditioning compressor in a restaurant in Dar es Salaam. The motor is rated at 3 HP, 415V, three-phase.
- You select a 415V contactor suitable for 3 HP load
- You set the thermal overload relay to the motor's full-load current (approximately 4.5A for a 3 HP motor)
- You wire the circuit so that pressing the Jog button runs the compressor briefly to check refrigerant pressure before full operation
- If the compressor runs continuously after pressing Start (without holding the button), you know the auxiliary contact is working correctly
- Always disconnect power before wiring
- Use proper PPE (boots, gloves, goggles)
- Ensure all connections are tight to prevent overheating
- Test the circuit with a multimeter before energizing
- Label all wires and components for easy identification
In Tanzania, refrigeration and air conditioning technicians use the jogging method when installing or maintaining split AC units in shops, offices, and guesthouses. For example, when testing a new 1.5-tonne split AC compressor in a Arusha hotel, a technician uses the jog button to run the compressor briefly — just long enough to check if the refrigerant pressure is normal before setting the thermostat. This prevents the compressor from running continuously with a fault, saving the client from expensive repairs.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
- Interpret control diagram
- Identify types and ratings of machine control
- Mark the location for installing the machine control systems
- Install the machine control
- Terminate cables
- Test the machine control
- Clean the work place
- Store tools, equipment and safety gears
Tathmini ya matokeo
The machines control installed and functions as per technical manufacturer’s manual specifications
Tathmini ya maarifa
Knowledge Evidence:
Detailed knowledge of:
Method used: The student should explain how to:
- Install single phase machine control
- Install three phase machine control (c) Principles: The student should explain the principles of operating machine control
Theories: The student should explain:
- Types of machine control
- Major parts of machine control
- Power rating of machine control
- Application and importance of machine control
Circumstantial knowledge:
Detailed knowledge about:
- Safe handling of machine controls
- First aid
Swali
What is the primary purpose of the jogging method in motor control?
Ingia ili kuwasilisha jibu lako na lihesabiwe katika umahiri wako.