Mada za sehemu hiiInstalling cold roomMada 6
- Installing condensing unit on slab
- Installing indoor unit
- Installing piping circuit
- Installing supply circuit
- Installing electric control circuit
- Charging with refrigerant and commissioning the system
Charging with Refrigerant and Commissioning the System
Charging a refrigeration or air conditioning system means adding the correct amount of refrigerant into the closed circuit. Commissioning means testing and adjusting the system to ensure it operates efficiently, safely, and according to the manufacturer's specifications. Together, these steps complete the installation of a cold room or air conditioning unit.
A correctly charged system delivers the required cooling capacity, consumes the right amount of energy, and lasts longer without breakdowns.
Refrigerant is the working fluid that absorbs heat from the conditioned space and releases it outside. If the system has:
- Too little refrigerant — cooling capacity drops, compressor runs hotter, and energy consumption increases.
- Too much refrigerant — the system becomes inefficient, high pressure rises dangerously, and the compressor may be damaged.
Only the exact charge specified by the manufacturer ensures proper operation.
1. Preparation
- Ensure all joints are tight and leak-free.
- Connect the charging cylinder to the service port on the low-pressure side of the manifold.
- Open the cylinder valve and the manifold valves slightly.
- Run the system in cooling mode so the compressor pumps refrigerant into the system.
2. Adding Refrigerant Gradually
- Watch the low-side pressure on the gauge.
- Add refrigerant slowly until the pressure reaches the value specified in the manufacturer's data (usually between 4–6 bar for R-134a in a medium-temperature system).
- Observe the sight glass to confirm that only refrigerant vapor (not liquid) enters the system.
3. Checking Subcooling and Superheat
- Subcooling is the cooling of liquid refrigerant below its saturation temperature. A good value is 5–7°C below the high-side pressure corresponding temperature.
- Superheat is the heating of vapor above its saturation temperature at the compressor inlet. Typical values are 5–8°C.
If these values are outside the recommended range, adjust the refrigerant charge accordingly.
Commissioning begins after charging is complete. Follow these checks:
- Measure running current — use a clamp meter or multimeter. The ampere reading must match the nameplate value (e.g., 5.2 A for a small split unit).
- Check refrigerant pressures — low side should be 4–6 bar, high side 15–18 bar (for R-134a at normal room temperature).
- Test for leaks — use an electronic leak detector or soap solution around all joints.
- Inspect airflow — ensure the evaporator fan draws air properly across the coil.
- Measure temperature difference — between supply and return air. A difference of 8–12°C indicates good performance.
- Record all readings — write them in the commissioning log for future reference.
- Wear safety goggles and gloves when handling refrigerants.
- Never overcharge the system — high pressure can cause pipes to burst.
- Ensure the area is well-ventilated; refrigerant vapors displace oxygen.
- Keep a fire extinguisher nearby when using any heat-producing tools.
A small cold room uses R-134a refrigerant. The manufacturer specifies a charge of 2.5 kg and a running current of 8.5 A. During commissioning, you measure:
- Low-side pressure: 4.2 bar
- High-side pressure: 16.8 bar
- Running current: 8.3 A
- Temperature difference (supply to return air): 10°C
Analysis:
- Pressures are within the normal range for R-134a.
- Current (8.3 A) is slightly below nameplate (8.5 A) but acceptable — this may indicate the system is slightly undercharged or the voltage is slightly low.
- Temperature difference of 10°C shows good cooling performance.
Conclusion: The system is properly commissioned. The slight current difference is within tolerance, but the technician should recheck the refrigerant charge if cooling performance drops over time.
In Tanzania, many small businesses — such as fish vendors in Kigoma or butchers in Dodoma — rely on small cold rooms to preserve perishable goods. When a technician installs or repairs such a system, correctly charging it with refrigerant and commissioning it ensures the cooler keeps food fresh without running up expensive electricity bills. A poorly charged system can cause a 1,500,000 TSh loss in spoiled fish in just one week, making proper charging a valuable skill for any refrigeration technician working in local markets.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Read and interpret installation drawings
- Select tools and equipment
- Perform diagnostic trouble shooting
- Perform modifications to suit site conditions
- Grout and fix foundation bolts
- Position major components in accordance with drawings, design specifications and instructions
- Test run the equipment
- Produce documentation in accordance with work site procedures
- Clean the workplace and tools
- Store tools and equipment
Tathmini ya matokeo
A record of values of pressure, temperature and electrical quantities conforming to the specified ratings
Tathmini ya maarifa
Knowledge Evidence:
Detailed knowledge of:
Method used: The student should explain how to:
- Perform levelling of equipment
- Prepare installation site
- Install the various components
- Perform test run
- Fabricate copper tubing
- Procedurally install or erect machinery
Principles: The student should explain the principles of: (p) Making an alignment (q) Temperature controls (r) Levelling a machine (s) Test running equipment
Theories: The student should explain:
- Different preservation temperatures for different items
- Use of installation drawings
- Importance of control systems
- Verification of acceptable performances of equipment
- Machinery erection procedures
Circumstantial knowledge:
Detailed knowledge about:
- Installation codes of practice
- Documented safety procedures and safety plans for personal and work site safety
- Safe handling of tools, measuring instruments and materials
Swali
What does charging a refrigeration system mean?
Ingia ili kuwasilisha jibu lako na lihesabiwe katika umahiri wako.
Ingia ili kufanya mazoeziMwalimu
Umekwama? Niulize chochote kuhusu mada hii.
Ingia ili kumuuliza Mwalimu wa AI wa Sonza kuhusu swali hili.
Ingia ili kuulizaMajadiliano
Hakuna maswali bado