Mada za sehemu hiiRepairing liquid coolersMada 4
- Replacing compressor unit
- Repairing electrical circuits
- Replacing evaporator coils
- Replacing circulation pump
An evaporator coil is a key component in a refrigeration system that absorbs heat from the space to be cooled. It is part of the evaporator unit where liquid refrigerant evaporates (changes from liquid to gas) by absorbing heat from the surrounding air or product. In liquid coolers, the evaporator coil cools water or other liquids that circulate through the system. When the coil becomes faulty — due to leaks, corrosion, or blockages — the cooling efficiency drops, and the entire coil must be replaced to restore proper operation.
Evaporator coils may need replacement when they develop leaks, become clogged with debris or ice, or suffer corrosion that reduces their ability to transfer heat. In liquid coolers specifically, a damaged coil can cause insufficient cooling of the liquid, leading to spoilage of stored products. Replacing the coil restores the system's cooling capacity and ensures food or beverages stay fresh.
Before beginning any work on refrigeration systems, always observe these safety measures:
- Wear safety boots, overalls, and gloves to protect against injuries and refrigerant exposure
- Ensure the system is disconnected from the power supply before starting
- Handle refrigerants with care — they can cause frostbite and are harmful to the environment
- Use proper lifting techniques when moving heavy components
- Keep the work area clean and free of oil, grease, or water to prevent slips
The following tools are required for replacing evaporator coils:
- Electro mechanical tool kit (screwdrivers, pliers, wrenches)
- Tube cutter for removing old copper tubing
- Spring bender for bending refrigerant lines without kinking
- Swaging tool for preparing new tube ends
- Oxy-acetylene welding set for brazing new connections
- Gauge manifold for checking system pressures
- Vacuum pump for removing moisture and air from the system
- Refrigerant leak detector for testing joints after installation
- Tape measure and scribers for marking and measuring
- Safety gear: boots, overalls, and gloves
Step 1: Diagnose and Confirm the Fault
Before replacing the coil, verify that the evaporator coil is indeed the problem. Check for visible signs of damage such as frost buildup, oil stains (indicating leaks), or corrosion. Use the gauge manifold to compare high and low side pressures — abnormal readings often point to a faulty evaporator. If the coil is leaking or blocked, it must be replaced.
Step 2: Recover the Refrigerant
Before disconnecting any pipes, the refrigerant must be safely recovered using a recovery machine or the gauge manifold. This prevents release into the atmosphere and complies with environmental regulations. Never release refrigerant into the air, as it damages the ozone layer.
Step 3: Remove the Old Evaporator Coil
- Disconnect the power supply to the refrigeration unit.
- Drain any liquid from the system if necessary.
- Use the tube cutter to cut the refrigerant lines connected to the evaporator coil. Make clean cuts to avoid debris entering the system.
- Remove the mounting fasteners holding the coil in place.
- Carefully extract the old coil from the unit.
Step 4: Prepare the New Evaporator Coil
- Inspect the new coil for any damage before installation.
- Use the spring bender to bend the connecting tubes to the correct angle, ensuring smooth flow paths.
- Use the swaging tool to prepare the tube ends for brazing, creating a proper fit.
Step 5: Install the New Coil
- Position the new evaporator coil in the unit, aligning it with the original mounting points.
- Secure the coil with the appropriate fasteners.
- Braze the refrigerant connections using the oxy-acetylene welding set. Apply proper brazing techniques to create leak-proof joints.
- After brazing, allow the joints to cool naturally — do not use water to speed cooling, as this can cause cracks.
Step 6: Test for Leaks and Evacuate the System
- Use the refrigerant leak detector to check all brazed joints for leaks. If bubbles appear, re-braze the joint.
- Connect the vacuum pump to the system and run it for at least 30 minutes to remove moisture and air. This is essential for proper operation.
- After evacuation, close the vacuum pump valves and monitor the system pressure to ensure it holds vacuum.
Step 7: Charge with Refrigerant
- Connect the refrigerant cylinder to the gauge manifold.
- Charge the system with the correct type and amount of refrigerant as specified by the manufacturer.
- Start the system and check that cooling begins normally.
Step 8: Final Inspection
- Verify that the evaporator coil is frosting and absorbing heat properly.
- Check all joints again for leaks.
- Ensure the liquid cooler is operating within normal temperature ranges.
A small restaurant in Arusha has a liquid cooler that is not cooling their stored drinks. The technician tests the system and finds a low-side pressure of 45 psi (normal is 70–90 psi), indicating the evaporator is not functioning properly. Upon inspection, a small oil stain near the evaporator coil connection confirms a refrigerant leak. The technician decides to replace the evaporator coil.
The technician recovers the old refrigerant, removes the damaged coil, installs a new coil using the tube cutter, spring bender, and braze connections with the oxy-acetylene set. After leak testing, evacuating the system for 30 minutes, and recharging with R-134a refrigerant, the system returns to normal operation. The liquid cooler now maintains a temperature of 4°C, keeping the drinks properly chilled.
- Forgetting to recover refrigerant before opening the system — this harms the environment and may be illegal
- Failing to evacuate the system properly, leading to moisture contamination and poor performance
- Using incorrect refrigerant type or amount, which reduces efficiency and may damage the compressor
- Not checking for leaks after installation, causing refrigerant loss and system failure
In Tanzania, many small businesses such as fish mongers in Dar es Salaam, butcher shops in Dodoma, and beverage vendors in Mwanza rely on liquid coolers and refrigeration units to keep their products fresh. If the evaporator coil develops a leak or stops cooling, the owner may lose hundreds of thousands of shillings in spoiled goods. Knowing how to replace an evaporator coil allows a technician to restore the cooler quickly, saving the business owner from costly losses and keeping fish, meat, and drinks safe for customers.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
- Select tools and equipment
- Perform diagnostic trouble shooting of evaporator coils
- Replace evaporator coil
- Charge refrigerant
- Test run
- Clean workplace
- Store tools and equipment
Tathmini ya matokeo
Demonstrate the ability of identify fault of evaporator coils and replace evaporator coils in liquid cooler conforms to technical specifications
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to:
- Control refrigerant being charged
- Perform leak detection
- Join copper tubing
Principles: The student should explain the principles of:
- Basic refrigerant cooling cycle
Theories: The student should explain:
- Replace concept
- Liquids
Detailed knowledge about:
- Different copper tube application
- Refrigerant properties
- Piping circuits
- Safe handling of refrigerants and tools
Swali
What is the primary function of an evaporator coil in a refrigeration system?