Mada za sehemu hiiPerforming rewinding of transformersMada 3
- Rewinding single-phase transformer
- Rewinding three-phase transformer
- Rewinding auto-transformer
Rewinding Three-Phase Transformers
A three-phase transformer is a static electrical device that transfers electrical energy between two or more circuits through electromagnetic induction. It is commonly used in industrial and commercial installations in Tanzania to step up or step down voltage levels for power distribution. When the windings of a three-phase transformer become damaged due to overheating, short circuits, or aging, rewinding becomes necessary to restore the transformer to working condition.
Types of Three-Phase Transformer Connections
- Star (Y) connection — one end of each winding connected together at a neutral point
- Delta (Δ) connection — the end of each winding connected to the start of the next winding
Why Rewinding is Necessary
- Winding insulation breaks down due to excessive heat
- Short circuits caused by moisture or physical damage
- Open circuits in the winding due to corrosion or mechanical stress
- To change the voltage rating for a different application
1. Assessment and Documentation
Before beginning any work, examine the transformer nameplate to record:
- Rated voltage (primary and secondary)
- Rated current
- Power rating in kVA
- Connection type (Star or Delta)
Measure and record the existing winding dimensions, number of turns, and wire gauge.
2. Disassembly
- Remove the transformer from its housing
- Carefully take out the core laminations
- Label each winding phase (Phase A, B, and C) to ensure correct reassembly
- Clean the core thoroughly using slot cleaning brushes
3. Winding Removal
- Use coil tripping chisels and wedges to remove damaged windings
- Count and record the exact number of turns for each phase
- Measure the wire diameter using a digital calliper
- Note the winding direction (clockwise or counter-clockwise)
4. Winding Reconstruction
- Prepare new copper wire of the same gauge as the original
- Wind new coils using the same number of turns and direction
- Use proper insulation between layers (paper or cellulose)
- Ensure even tension while winding to avoid loose coils
5. Reassembly
- Reinsert the core laminations carefully
- Secure the windings in place
- Apply proper phasing connections (A, B, C)
- Test for continuity and insulation resistance
6. Testing
- Use a multimeter to check for continuity in each phase
- Perform an insulation resistance test using a megohmmeter
- If possible, perform a no-load test to verify proper operation
A three-phase transformer has a primary voltage of 415 V and secondary voltage of 240 V. The primary has 500 turns. Calculate the required number of turns for the secondary winding.
Using the transformer turns ratio formula:
NsNp=VsVp
Where:
- Np = primary turns = 500
- Vp = primary voltage = 415 V
- Vs = secondary voltage = 240 V
- Ns = secondary turns (unknown)
Solving for Ns:
Ns=VpNp×Vs=415500×240=415120000≈289 turns
Therefore, the secondary winding requires approximately 289 turns of wire.
- Always disconnect the transformer from the power supply before starting work
- Wear insulated gloves and safety goggles
- Use proper lifting techniques when handling heavy transformer cores
- Keep the work area clean and free of flammable materials
- Use propane torches and grinding tools in well-ventilated areas only
- Electrician's tool kit
- Digital calliper for precise measurements
- Coil tripping chisels and wedge removers
- Slot cleaning brushes
- Wire cutters and strippers
- Hammers and mallets
- Insulation testing equipment
In Tanzania, many small industries in areas like Arusha, Mwanza, and Dodoma use three-phase transformers to operate heavy machinery from the single-phase mains supply. When a transformer's windings fail due to overload or age, rewinding it locally saves the cost of buying a new transformer — which can cost over TSh 1,500,000. A local electrician with rewinding skills can restore the transformer for a fraction of that price, keeping small businesses running without expensive downtime.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Select tools, equipment, and safety gear.
- Record nameplate data.
- Strip transformer (dismantle laminations).
- Remove old winding and note down the number of turns.
- Determine wire size.
- Clean magnetic core.
- Design a new bobbin.
- Wind new coil.
- Bind the coil and varnish the winding.
- Set transformer for curing. Perform necessary tests for verification of termination.
- Test the rewound transformer as per technical standards and IEE Regulations.
- Observe safety precautions.
- Clean tools, equipment, and work area.
Tathmini ya matokeo
Three-phase transformer rewound as per technical specifications, and IEE Regulations.
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to rewind three-phase transformers.
Principles: The student should explain the principles related to rewinding of three-phase transformers.
Theories: The explain:
- Types of windings.
- Taking Data and calculations.
- Core Testing.
- Winding stripping procedures.
- Coil making. insulation.
- Internal connections
- Testing untreated and treated treatment.
Detailed knowledge about:
- Safety precautions when handling transformers.
- Properties of materials
Swali
What are the two main types of connections used in three-phase transformers?