Mada za sehemu hiiPerforming rewinding of transformersMada 3
- Rewinding single-phase transformer
- Rewinding three-phase transformer
- Rewinding auto-transformer
A single-phase transformer may need rewinding when its windings burn out due to overload, short circuits, or aging. Rewinding is the process of removing the damaged coils and replacing them with new ones of the correct size and number of turns to restore the transformer to working condition.
- Switch off, unplug or isolate the transformer from any power source, and prove it dead, before handling it. Never work on a transformer that is connected to the supply
- Wear safety goggles to protect eyes from wire fragments
- Use insulated tools only
- Work in a well-ventilated area away from flammable materials
- Keep the workspace clean and organised
- Varnish and thinners are flammable and give off harmful vapour: no naked flames nearby, and keep the lid on the tin
- Laminations have sharp edges: wear gloves when handling them
- Electrician's tool kit
- Coil tripping chisel
- Wire cutters and wire strippers
- Digital calliper (for measuring wire diameter)
- Bobbin holder
- Slot cleaning brushes
- Power hand drill
- Slotting files
- Wedge removers
- Hammers and mallets
- Coil making machine with a turns counter
- Multimeter and insulation tester (megger)
- In a shell-type transformer, the kind found in most small equipment, both windings sit on one bobbin on the centre limb of a stack of E and I laminations. In a core-type transformer the windings are on the outer limbs.
- Concentric (layer) windings are wound one over the other on the same bobbin. Sandwich (split-bobbin) windings sit side by side in separate sections.
- A step-down transformer has more turns on the primary than on the secondary; a step-up transformer has fewer.
- The wire is copper covered with enamel insulation. The laminations are thin sheets of silicon steel, each insulated on its surface to reduce eddy-current losses.
Step 1 — Recording the Data
Before removing any windings, record all transformer data:
- Rated power (VA) and frequency from the nameplate
- Primary and secondary voltages
- Primary and secondary currents
- Number of turns on each winding (counted when the old winding is removed in Step 3)
- Wire gauge (diameter) of each winding (measured in Step 3)
- Core cross-sectional area
This information is essential for rewinding the transformer correctly.
Step 2 — Dismantling, Core and Bobbin Inspection
Carefully disassemble the transformer:
- Remove the clamp or frame, then tap out the laminations one at a time with a mallet and a thin drift, noting how the E and I pieces are interleaved. The first few are tight; take care not to bend them
- Take out the damaged bobbin or coil former
- Inspect the laminations for rust, burrs, bent plates or burnt patches, and clean them with a brush and a dry cloth. Keep every lamination: the full stack is needed
- Clean the bobbin with a brush once the old wire is off (Step 3)
- Check that the bobbin is not cracked, warped or burnt. If it is, design a new one: measure the width of the centre limb, the height of the lamination stack and the size of the window with the digital calliper, then cut and glue a bobbin from insulating board so that it slides snugly onto the centre limb and its cheeks fit inside the window
Step 3 — Removing Old Windings
- Note which winding is on the outside, where each lead comes out and the direction of winding
- Remove the outer tape and insulation, then unwind the old wire, one winding at a time. Mounting the bobbin on the coil making machine and turning it backwards lets the counter count the turns for you
- Count and record the exact number of turns removed from each winding, and note any tappings
- Scrape the enamel from a piece of each wire and measure its diameter with the digital calliper
- Where a coil is too badly burnt to unwind, cut it off with the coil stripping chisel or wire cutters and work out its turns from the turns per volt of the other winding and the voltage on the nameplate
Step 4 — Preparing New Windings
Calculate or determine the correct wire size:
- Use new enamelled copper wire of the same diameter as the wire removed from each winding
- Use the digital calliper to verify that the diameter of the new wire matches what you recorded
- Leave enough wire at the start and finish of each winding for connections, and protect these leads with sleeving
For a step-down transformer, the primary winding has more turns with thinner wire, while the secondary winding has fewer turns with thicker wire. This is because the secondary carries the larger current.
Step 5 — Winding the Coils
Wind the coils onto the bobbin following these rules:
- Wind in the same direction as the original winding
- Keep turns tight and uniform with no overlapping
- Use a coil making machine or hand winding technique
- Insert insulating paper between layers, and several layers of insulation between the primary and the secondary winding, because this insulation separates the mains voltage from the low-voltage side
- Finish by binding the completed coil with insulating tape
- Count each turn accurately
Step 6 — Testing the Windings
Before reassembly, test the new windings:
- Use a multimeter to check for continuity in both windings
- Verify there is no short between primary and secondary windings
- Measure the resistance of each winding
- Check insulation resistance between the two windings with an insulation tester (the test to the core is done after reassembly)
Step 7 — Reassembly
- Dip the bound coil in insulating varnish, or brush the varnish on, and let it drain
- Set the coil to cure: bake it in an oven, or leave it in a warm, dry, ventilated place, for the time the varnish maker states, until the varnish is hard
- Refit the laminations into the bobbin, interleaving the E and I pieces alternately as they were, until the whole stack is back; tap them level with a mallet and refit the clamp
- Solder the leads to their terminals and insulate the joints with sleeving
- Mount the transformer back in its housing and reconnect the earth to the core or frame
A single-phase transformer has the following data recorded before rewinding:
- Primary voltage: 230 V
- Secondary voltage: 12 V
- Primary turns counted: 920 turns
- Secondary winding: too badly burnt to count
- Secondary full-load current: 5 A
Calculation for the new secondary winding:
Turns per volt =230920=4 turns per volt
Secondary turns =4×12=48 turns
Check with the turns ratio: 12230=19.2 and 48920=19.2, so the voltages and the turns are in the same ratio.
Primary current at full load, ignoring losses =23012×5=0.26A
The primary carries only about 0.26 A while the secondary carries 5 A. This is why the primary of a step-down transformer is wound with thin wire and the secondary with thick wire. Use wire of the same diameter as the original for each winding, and wind in the same direction as the original.
After rewinding, perform the following tests:
- Continuity test — All windings must show complete circuit
- Test for a short between windings — Multimeter should show infinite resistance between primary and secondary
- Insulation test — Use a 500 V insulation tester between the windings and between each winding and the core; each reading should be at least 1 MΩ, and a sound new winding reads far higher
- No-load test — With the terminals covered, the core earthed and the supply taken through a fuse, connect the primary to its rated voltage under supervision and measure the secondary voltage. With no load it should be slightly above the rated secondary voltage. Make and change all connections with the supply switched off and unplugged
Carry out the continuity and insulation tests before varnishing and again after curing, so that a fault can be put right while the wire is still easy to reach.
- Collect the old copper wire and sell it to a scrap dealer for recycling; never burn it
- Put old insulation, tape and rags soaked in varnish into a closed metal bin, away from heat
- Close the varnish tin, clean the brushes, wipe the tools and return them to the store
- Sweep the bench and floor so that no wire clippings are left
In Tanzania, small electrical shops in markets such as Kariakoo in Dar es Salaam or Mwanza often repair transformers found in old radio sets, battery chargers, and voltage stabilisers. A student who learns rewinding can start a small business rewinding burnt transformers for customers, saving clients the cost of buying entirely new equipment.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Select tools, equipment, and safety gear.
- Record nameplate data.
- Strip transformer (dismantle laminations).
- Remove old winding and note down the number of turns.
- Determine wire size.
- Clean magnetic core.
- Design a new bobbin.
- Wind new coil.
- Bind the coil and varnish the winding.
- Set the transformer for curing.
- Perform necessary tests for verification of termination.
- Test the rewound transformer as per technical standards and IEE Regulations.
- Observe safety precautions.
- Clean tools, equipment, and work area.
Tathmini ya matokeo
Single-phase transformer rewound as per technical specifications, and IEE Regulations.
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to rewind single-phase transformers.
Principles: The student should explain the principles relating to rewinding of a single-phase transformer.
Theories: The student should explain:
- Types of transformer windings.
- Taking data and calculation.
- Core testing.
- Winding stripping procedures.
- Coil making.
- Winding insulation.
- Internal connections.
- Testing untreated and treated windings.
- Winding treatment.
Circumstantial knowledge:
Detailed knowledge about:
- Safety precautions when handling transformers.
- Properties of materials
Swali
A burnt transformer is still wired into a battery charger. What must be done before the transformer is handled?
Ingia ili kuwasilisha jibu lako na lihesabiwe katika umahiri wako.
Ingia ili kufanya mazoeziMwalimu
Umekwama? Niulize chochote kuhusu mada hii.
Ingia ili kumuuliza Mwalimu wa AI wa Sonza kuhusu swali hili.
Ingia ili kuulizaMajadiliano
Hakuna maswali bado