Mada za sehemu hiiInstalling switch gearsMada 3
- Installing three phase distribution board
- Installing change over switches
- Installing power factor correction facilities
Power factor (PF) is a measure of how effectively electrical power is being used in an AC circuit. It is the ratio of real power (working power) to apparent power (total power supplied). A low power factor means that electrical power is not being used efficiently, leading to higher electricity costs and strain on the electrical system.
In an AC circuit, there are three types of power:
Real power (P) — measured in kilowatts (kW), is the power that actually does useful work, such as turning a motor or lighting a bulb. This is like the water in the glass.
Reactive power (Q) — measured in kilovolt-amperes reactive (kVAR), is the power that flows back and forth between the source and the load without doing useful work. This is like the foam on top of the water.
Apparent power (S) — measured in kilovolt-amperes (kVA), is the total power supplied by the source, which is the combination of real power and reactive power. This is like the total content of the glass (water plus foam).
The relationship between these three powers is expressed by the power triangle:
S=P2+Q2
And power factor is calculated as:
PF=SP=cosθ
Where θ is the phase angle between voltage and current.
A low power factor indicates that a large portion of the apparent power is reactive power, which does not perform useful work but still burdens the electrical system. In Tanzania, TANESCO charges penalties for installations with low power factor because:
- Increased current flow — Low PF causes higher currents to flow through wires and cables, leading to greater power losses as heat.
- Overloading of equipment — Transformers, cables, and switchgear must be oversized to handle the extra current.
- Higher electricity bills — Reactive power consumption incurs additional charges.
Inductive loads are the primary cause of low power factor in most electrical installations. These loads include:
- Electric motors — AC induction motors found in factories, water pumps, and refrigeration units
- Fluorescent lighting — Common in commercial buildings
- Transformers — Used in power distribution
- Welding machines — Common in workshops
These loads cause the current to lag behind the voltage, creating a phase difference that reduces the power factor.
Power factor correction involves adding devices that provide capacitive (leading) reactive power to cancel out the inductive (lagging) reactive power. This brings the power factor closer to 1 (or unity).
Types of Power Factor Correction Devices
Capacitor banks — These are groups of capacitors connected together. Capacitors provide leading reactive power that offsets the lagging reactive power from inductive loads. Capacitor banks can be:
- Fixed capacitor banks — Permanently connected to the system
- Automatic capacitor banks — Switched in stages based on the load
Synchronous motors — These can operate at leading power factor when over-excited, providing reactive power compensation.
Static VAR compensators — Advanced solid-state devices that provide fast reactive power compensation.
When installing power factor correction equipment, follow these safety and installation steps:
Safety Measures
- Always switch off the main power supply before installation
- Use insulated tools and wear appropriate PPE (safety goggles, overall, safety boots)
- Ensure the work area is dry and free from obstructions
- Follow the manufacturer's instructions strictly
- Use lockout/tag-out procedures to prevent accidental switching on
Installation Procedure
-
Assess the installation — Determine the current power factor and the reactive power requirement using measurements or electricity bills.
-
Select appropriate correction devices — Choose capacitor banks with the correct rating (measured in kVAR) for the installation.
-
Choose installation location — Install capacitor banks near the inductive loads or at the main distribution board for overall correction.
-
Mount the equipment — Securely mount the capacitor bank enclosure using appropriate fixings (rawl plugs, screws).
-
Connect the wiring — Connect the capacitor bank to the electrical system following the wiring diagram. Ensure:
- Phase conductors are connected correctly
- Grounding is properly done
- All connections are tight and secure
-
Test the installation — After inspection and approval, test the power factor correction to ensure it operates correctly and achieves the desired PF.
-
Label and record — Label all components and keep records of the installation for future maintenance.
A small workshop in Arusha has the following electrical loads:
- Total real power: 15 kW
- Apparent power: 20 kVA
Calculate the current power factor:
PF=SP=2015=0.75
This low power factor means the workshop is using power inefficiently. To improve the power factor to 0.95, we need to calculate the required capacitor rating.
Step 1: Find the current reactive power:
Qinitial=S2−P2=202−152=400−225=175=13.23 kVAR
Step 2: Find the target apparent power for PF = 0.95:
Starget=0.95P=0.9515=15.79 kVA
Step 3: Find the target reactive power:
Qtarget=Starget2−P2=15.792−152=249.3−225=24.3=4.93 kVAR
Step 4: Calculate the required capacitor rating:
Qcapacitor=Qinitial−Qtarget=13.23−4.93=8.3 kVAR
Therefore, a capacitor bank of approximately 8.5 kVAR should be installed to improve the power factor to 0.95.
In Tanzania, many small businesses such as maize mills, welding workshops, and grocery shops use single-phase and three-phase electric motors. These inductive loads cause low power factor, leading to higher electricity bills from TANESCO. By installing a capacitor bank to correct the power factor, a shop owner in Morogoro can reduce their monthly electricity costs by up to 15% and avoid penalty charges, while also reducing strain on their wiring and extending the life of their electrical equipment.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The students should be able to explain how to:
- Interpret single line and lay out drawings.
- Select tools, equipment and safety gear
- Install power factor facilities.
- Observe safety precautions
- Clean the work area.
- Collect all tools and other items for storage.
Tathmini ya matokeo
Power factor correction facilities are installed as per and IET regulations.
Tathmini ya maarifa
Knowledge evidence: Detailed knowledge
Methods used: The students should explain how to: Install power factor facilities.
Principles: The students should be able to demonstrate the correct procedures for installing power factor correction facilities Theory: the students should explain:
- Inductive and resistive load
- Apparent power, active power and reactive power
- Power factor
- Methods of correcting
Swali
What does a low power factor indicate about an electrical installation?
Ingia ili kuwasilisha jibu lako na lihesabiwe katika umahiri wako.
Ingia ili kufanya mazoeziMwalimu
Umekwama? Niulize chochote kuhusu mada hii.
Ingia ili kumuuliza Mwalimu wa AI wa Sonza kuhusu swali hili.
Ingia ili kuulizaMajadiliano
Hakuna maswali bado