Mada za sehemu hiiInstalling control system of AC machinesMada 7
- Installing DOL starter incorporating remote control
- Installing DOL by using the jogging method
- Installing forward and reverse starter
- Installing manual star-delta starter
- Installing automatic star-delta starter
- Installing a rotor resistance starter for the slip-ring motor with automatic starting
- Installing a rotor resistance starter for the slip-ring motor
A Direct-On-Line (DOL) starter is an electrical control device used to start an AC electric motor safely by connecting it directly to the full supply voltage. It also provides protection to the motor against electrical faults. This topic covers how to install a DOL starter with remote control capability and how to incorporate over-voltage and under-voltage protective devices.
A DOL starter is a simple and economical motor starter that connects an electric motor directly to the power supply through a set of contacts. When the start button is pressed, the contacts close and apply full line voltage to the motor terminals. The starter also includes overload protection that disconnects the motor if it draws too much current.
Key parts of a DOL starter include:
- Main contacts – Carry the motor current when closed
- Overload relay – Protects the motor from overcurrent
- Start and Stop push buttons – Provide manual control
- Coil – Energizes the contacts when the start button is pressed
- Enclosure – Houses and protects all components
The DOL starter is important in electrical installations for several reasons:
- Simple construction – Easy to understand, install, and maintain
- Low cost – Less expensive than other motor starters
- High starting torque – Provides full voltage to the motor for quick startup
- Motor protection – Prevents damage from overload, over-voltage, and under-voltage conditions
- Remote operation capability – Can be controlled from a distance using remote controls or auxiliary contacts
Voltage fluctuations can damage electric motors. Over-voltage occurs when the supply voltage exceeds the motor's rated voltage, causing excessive current and heat. Under-voltage occurs when the supply is too low, causing the motor to draw higher current and overheat.
Protective devices used with DOL starters include:
- Over-voltage relay – Monitors supply voltage and trips when it exceeds safe limits
- Under-voltage relay – Monitors supply voltage and trips when it falls below safe limits
- Combined voltage protection relay – Performs both functions in one device
These relays are connected in series with the starter coil. When abnormal voltage is detected, the relay trips and opens the control circuit, de-energizing the starter coil and disconnecting the motor from the supply.
The following steps describe how to install a DOL starter incorporating remote control and voltage protection:
-
Observe safety precautions – Wear safety boots, goggles, gloves, and overalls before starting any electrical work. Lock out and tag out the supply.
-
Mount the starter – Secure the DOL starter enclosure to a suitable position on the wall or panel using appropriate fasteners.
-
Connect the supply wires – Run the three-phase supply cables (L1, L2, L3) to the main terminals of the starter. Tighten all connections securely using a spanner.
-
Connect the motor wires – Run the motor cables from the starter output terminals to the motor junction box. Ensure correct phase connection.
-
Install voltage protection relays – Mount the over-voltage and under-voltage relays on the panel. Connect their normally open contacts in series with the starter coil circuit.
-
Connect the remote control circuit – Install remote start and stop buttons at the desired location. Wire them in parallel with the local push buttons but through the voltage protection contacts.
-
Test the installation – Before energizing, check all connections with a multimeter for continuity. Verify that the overload settings are correct for the motor rating.
-
Energize and test – Turn on the supply. Press the start button (local or remote) and verify that the motor runs. Test the voltage protection by simulating over-voltage or under-voltage conditions to ensure proper tripping.
A workshop in Arusha has a 3-phase induction motor rated at 7.5 kW. The motor is to be controlled by a DOL starter with remote push buttons located 15 metres away at the machine operator's station. An over-voltage relay set at 440V and an under-voltage relay set at 340V are to be installed for protection.
Solution:
-
Select a DOL starter with a contactor rated for at least 15A (to handle the 7.5 kW motor current of approximately 11A).
-
Set the overload relay to 125% of the motor full-load current (11A×1.25=13.75A, choose 14A setting).
-
Connect the voltage relays in series with the start button circuit so that if voltage goes outside the 340V–440V range, the coil circuit opens and the motor stops.
-
Wire the remote start and stop buttons at the operator's station in parallel with the local buttons. Use 1.5 mm² control cables for the remote circuit.
-
After installation, test by pressing the remote start button — the motor should run. Then temporarily apply a voltage above 440V to confirm the over-voltage relay trips and stops the motor.
This setup ensures the motor is protected from dangerous voltage conditions and can be started and stopped conveniently from the operator's station.
In many small workshops and factories across Tanzania, such as those in Kariakoo or along the Dar es Salaam industrial area, DOL starters are used to control water pump motors, compressor motors, and conveyor belt motors. A local technician might install a DOL starter with remote control at a poultry farm in Mwanza, allowing the farmworker to start and stop the water pump from the farm office while the voltage protection device safeguards the pump motor from power fluctuations common in rural electricity supplies.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Interpret the control diagram.
- Identify the types and ratings of machine control.
- Mark the location for installing the machine control systems.
- Install the machine control.
- Terminate cables.
- Test the machine control.
- Apply safety precautions.
- Clean the workplace.
Tathmini ya matokeo
The installed machine controls and functions as per standards.
Tathmini ya maarifa
Knowledge evidence: Detailed knowledge of:
Method used: The student should explain how to install a DOL starter incorporating remote control.
Principles: The student should explain the principles related to installing a DOL starter incorporating remote control.
Theories: The student should explain:
- The types of machine control.
- The major parts of machine control.
- The power rating of machine control.
- The application and importance of machine control.
Detailed knowledge about:
- Safe handling of machine controls. Maintenance of machines and equipment.
Swali
Which of the following is the main function of a Direct-On-Line (DOL) starter?