Mada za sehemu hiiInstalling control system of AC machinesMada 7
- Installing DOL starter incorporating remote control
- Installing DOL by using the jogging method
- Installing forward and reverse starter
- Installing manual star-delta starter
- Installing automatic star-delta starter
- Installing a rotor resistance starter for the slip-ring motor with automatic starting
- Installing a rotor resistance starter for the slip-ring motor
Installing DOL Starter Using the Jogging Method
Direct On-Line (DOL) starters are commonly used to start AC electric motors because they provide a simple and inexpensive way to connect the motor directly to the supply voltage. The jogging method (also called inching) is a control technique used with DOL starters to operate a motor in short bursts, which is useful for tasks that require precise positioning or repeated starting and stopping.
A Direct On-Line (DOL) starter is a simple motor starting device that connects an electric motor directly to the power supply through a set of contactors. When the start button is pressed, the main contacts close and apply full line voltage to the motor terminals.
A basic DOL starter circuit consists of:
- Main contactor – carries the load current to the motor
- Overload relay – protects the motor from overcurrent
- Start button – normally open (NO) contact
- Stop button – normally closed (NC) contact
- Mains supply – three-phase or single-phase AC
Jogging (also called inching) is a method of operating a motor where the operator holds a push button to run the motor for a short time, then releases it to stop. Each time the button is pressed, the motor runs for as long as the button is held down.
In the jogging method:
- The start button is mechanically or electrically latched to provide continuous running
- Jogging bypasses the latching mechanism, allowing momentary operation
- The motor runs only while the jog button is pressed
This method is commonly used for:
- Conveyor belt positioning
- Machine tool alignment
- Door opening and closing
- Any application requiring short, controlled movements
The jogging method in DOL starters provides several important benefits:
- Precise positioning – Allows operators to move equipment in small increments
- Safety – Operator can stop immediately by releasing the button
- Reduced wear – Prevents continuous running when only brief operation is needed
- Energy saving – Motor runs only when needed, not continuously
- Simplicity – The jogging circuit adds minimal complexity to the basic DOL starter
Required Tools and Equipment
- Set of screwdrivers
- Multimeter
- Set of spanners
- Combination pliers
- Safety boots, goggles, gloves, and overalls
Installation Steps
Step 1: Prepare the work area
- Ensure the workbench is clean and organized
- Switch off the power supply and verify with a multimeter
- Wear all required safety gear
Step 2: Mount the components
- Install the main contactor on the panel
- Mount the overload relay below the contactor
- Fit the start, stop, and jog push buttons on the enclosure
Step 3: Wire the main circuit
- Connect the three-phase supply (L1, L2, L3) to the main contacts of the contactor
- Connect the motor leads (U, V, W) from the overload relay to the motor
Step 4: Wire the control circuit
- Connect the stop button (NC) in series with the coil
- Connect the start button (NO) in parallel with the contactor auxiliary contact
- Connect the jog button (NO) directly across the start button, bypassing the latching contact
Step 5: Install protective devices
- Connect the overload relay in series with the main contacts
- Ensure proper grounding of the starter enclosure
Protective devices ensure the motor and control circuit operate safely under abnormal voltage conditions.
Over-voltage Protection
Over-voltage occurs when the supply voltage exceeds the rated value. This can damage motor insulation.
Protective devices:
- Voltage relay – detects excessive voltage and trips the circuit
- Surge arrester – protects against voltage spikes and transients
Under-voltage Protection
Under-voltage occurs when the supply voltage falls below the rated value. This can cause the motor to draw excessive current and overheat.
Protective devices:
- Under-voltage relay – trips the contactor when voltage drops below a set level
- Motor protection circuit breaker (MPCB) – provides combined overload and under-voltage protection
These devices are connected in the control circuit to ensure the motor stops safely when abnormal voltage conditions occur.
Scenario: A workshop in Dar es Salaam has a DOL starter with jogging for a drilling machine. The motor nameplate shows 400V, 50Hz, and 5kW. The operator needs to position the drill bit precisely for small holes.
Solution:
- The operator presses the jog button momentarily
- The main contactor closes and applies 400V directly to the motor
- The motor runs for a short time, moving the drill slightly
- When the button is released, the contactor opens and the motor stops
- The operator repeats this process until the drill bit reaches the exact position
This method allows precise control without running the motor continuously, saving energy and reducing wear on the machine.
- Always disconnect power before wiring or servicing
- Use appropriate PPE (boots, goggles, gloves, overalls)
- Test all connections with a multimeter before energizing
- Ensure all protective devices are properly set
- Follow lockout-tagout procedures
In Tanzania, the jogging method is commonly used in small workshops and factories. For example, a hardware store in Mwanza might have a DOL starter with jogging for a grinding machine. When shaping metal pieces, the operator uses the jog button to move the grinding wheel in short bursts, achieving precise shaping without running the motor continuously. This saves electricity (important when using prepaid Tanzania Electric Supply Company (TANESCO) meters) and extends the life of the grinding wheel.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Interpret the control diagram.
- Identify types and ratings of machine control.
- Mark the location for installing the machine control systems.
- Install the machine control.
- Terminate cables.
- Test the machine control.
- Apply safety precautions.
- Clean the workplace.
Tathmini ya matokeo
The installed machine control and functions as per standards.
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to install a DOL starter by using the jogging method.
Principles: The student should explain the principles related to installing a DOL by using jogging methods.
Theories: The student should explain:
- The types of machine control.
- The major parts of machine control.
- The power rating of machine control.
- The application and importance of machine control.
Detailed knowledge about:
- Safe handling of machine controls.
Swali
What is another name for the jogging method used with DOL starters?
Ingia ili kuwasilisha jibu lako na lihesabiwe katika umahiri wako.
Ingia ili kufanya mazoeziMwalimu
Umekwama? Niulize chochote kuhusu mada hii.
Ingia ili kumuuliza Mwalimu wa AI wa Sonza kuhusu swali hili.
Ingia ili kuulizaMajadiliano
Hakuna maswali bado