Mada za sehemu hiiInstalling control system of DC machinesMada 3
- Installing diverter in the armature
- Installing varistor in the field winding
- Starting a D.C. machine by using an autotransformer starter
A varistor is a voltage-dependent resistor used in DC machine field windings to protect the winding from dangerous voltage spikes (transients) that can destroy insulation and damage the machine.
A varistor is an electronic component whose resistance changes with the applied voltage. At normal operating voltage, its resistance is very high, so it draws almost no current. When a voltage spike (transient) occurs, its resistance drops sharply, allowing it to conduct and clamp the excess voltage to a safe level, protecting the field winding insulation.
DC machine field windings are inductive loads. When the supply is suddenly switched off, the collapsing magnetic field induces a high-voltage transient across the winding. Without protection:
- The insulation can break down
- Arcing can occur at the switch contacts
- The winding can be permanently damaged
The varistor absorbs this spike energy and limits the voltage to a safe value.
- Metal Oxide Varistor (MOV) — the most common type, made from zinc oxide granules. It offers excellent clamping characteristics and is widely used in DC machine protection.
- Silicon Carbide Varistor — older technology, less commonly used today.
1. Safety First
Before any work, switch off and wait until the machine has stopped completely. Isolate it from the power supply, lock the isolator in the off position and hang a warning tag on it. Then prove the field terminals dead with a voltage tester that has just been checked on a known supply. Wear safety goggles, safety boots, and gloves throughout the procedure.
2. Gather Tools and Equipment
- Multimeter
- Megger or insulation tester
- Combination pliers
- Screwdrivers (flat and Phillips)
- Spanner set
- Electrician's knife
- Varistor rated appropriately for the field winding voltage
3. Identify the Field Winding Terminals
Locate the two terminals of the field winding on the DC machine. These are usually clearly marked in the terminal box and shown on the control diagram (a shunt field is commonly marked E1 and E2, or F1 and F2). Use the multimeter to verify continuity across the winding and confirm correct identification.
4. Check the Varistor Rating
A varistor has three ratings on its data sheet. The maximum continuous working voltage must be higher than the highest normal voltage of the field winding, with a margin of about 20%, so that the varistor does not conduct in normal running. The clamping voltage, which is always higher than the working voltage, must be lower than the voltage the winding insulation can withstand. The energy rating (in joules) must be large enough to absorb the energy stored in the field. For example, for a field winding that operates at 220 V DC, choose a varistor with a continuous working voltage of at least 275 V DC, and take the energy rating from the manufacturer's manual for the machine.
5. Test the Varistor Before Installation
Use the multimeter to check the varistor in ohmmeter mode. It should show very high resistance (essentially open circuit), because the small voltage of the meter is far below its working voltage. Also look for cracks or burn marks on its body. If it shows low resistance, it may already be damaged and should be replaced.
6. Connect the Varistor Across the Field Winding
Using appropriate connectors and insulated leads:
- Connect one terminal of the varistor to one field winding terminal.
- Connect the other terminal of the varistor to the other field winding terminal.
- Ensure connections are tight and secure using a spanner or screwdriver as required.
- The varistor is connected in parallel with the field winding. It has no polarity, so it can be connected either way round.
- Fix the varistor inside the terminal box or on the control panel, as close to the field terminals as possible, with short leads kept clear of moving parts.
7. Insulate All Connections
Use insulating tape or heat-shrink sleeving on all bare conductors and terminals to prevent accidental short circuits.
8. Test the Installation
- Use the megger to test insulation resistance between the field winding and the machine frame — it should be at least 1 MΩ. Do not apply the megger across the two field terminals: its test voltage would make the varistor conduct, giving a false low reading and possibly damaging the varistor.
- Use the multimeter to confirm the varistor is properly connected and no short circuits exist.
- When the tests are satisfactory and the work has been checked by your supervisor, remove the lock and tag, restore the supply and observe the machine during start-up and shutdown for any abnormal behaviour. Keep the terminal box cover fitted and never touch the terminals while the supply is on.
In some workshops the word varistor is also used loosely for a variable resistor. A variable resistor in the field circuit, properly called a field regulator or field rheostat, does a different job: it controls speed.
- It is connected in series with the shunt field winding, not in parallel.
- Increasing its resistance reduces the field current and weakens the field, so the motor runs faster than its normal speed. Reducing the resistance brings the speed back down.
- It is rated by its resistance range and by the field current it must carry. It is fixed on the control panel with its metal case earthed.
- The field circuit of a running shunt motor must never be opened or left with a loose connection. If the field current is lost, the motor can race to a dangerous speed. Always start the motor with the field regulator at minimum resistance (full field).
- Three basic types: series (field in series with the armature; very high starting torque; cranes, hoists, traction), shunt (field in parallel with the armature; nearly constant speed; lathes, fans, pumps) and compound (both fields; presses, lifts, rolling mills).
- Speed: N∝ΦEb, where Eb is the back EMF and Φ the field flux. Speed regulation is the change in speed from no load to full load, as a percentage of the full-load speed.
- Commutation: the commutator and brushes reverse the current in each armature coil as it passes a brush, so that the torque always acts in one direction. Poor commutation shows as sparking.
- Armature reaction: the magnetic field of the armature current distorts and weakens the main field, shifting the neutral axis and causing sparking unless interpoles are fitted.
A DC shunt motor has a field winding rated at 240 V DC. During normal operation the field winding shows 240 V. A technician selects an MOV varistor with a maximum continuous working voltage of 300 V DC. The technician:
- Disconnects power, locks out the isolator and proves the field terminals dead.
- Identifies the two field winding terminals.
- Tests the varistor — it shows very high resistance (good condition).
- Connects the varistor in parallel across the field winding terminals.
- Insulates all connections.
- Uses the megger between the field winding and the frame to verify insulation resistance is above 1 MΩ.
- Reconnects power — the motor runs normally, and voltage spikes at switch-off are now suppressed.
- The varistor is always connected in parallel with the field winding.
- It acts only during voltage transients; at normal voltage it draws negligible current.
- Always check the varistor rating matches the field winding voltage before installation.
- Never install a varistor whose continuous working voltage is below the normal operating voltage; it would conduct all the time, overheat and fail.
- Never apply an insulation tester across the varistor itself.
- Do not confuse the varistor (in parallel, for protection) with the field regulator (in series, for speed control).
- Always observe full safety procedures throughout the installation.
When the job is finished, collect the off-cuts of cable, sleeving and tape, put scrap copper aside for recycling, wipe the tools and return them to the store, and put the meters back in their cases.
In a small workshop in Arusha that uses a DC motor-driven grinding machine, voltage spikes from switching the motor on and off can gradually destroy the field winding insulation, leading to costly downtime and repairs. By installing a properly rated varistor across the field winding, the electrician protects the motor, extends its lifespan, and saves the workshop owner the cost of a replacement motor.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Interpret control diagrams.
- Identify types and ratings of D.C. machine controls.
- Prepare the base of D.C. machine control.
- Mark the location for installing the D.C. machine control systems.
- Fix and align the D.C. machine control.
- Install and terminate cables of the D.C. machine control.
- Test the D.C. machine control.
- Apply safety precautions.
- Clean the workplace.
Tathmini ya matokeo
D.C. machines control fixed, installed, and functions as per the manufacturer’s manual specifications.
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to install a varistor in the field winding.
Principles: The student should explain the principles relating to installing varistor in the field winding.
Theories: The student should explain:
- The three basic types of D.C. machines.
- The commutation process.
- Speed regulation applied to D.C. machines.
- The armature reaction in D.C. machines.
- The Application of different types of D.C. machines.
Circumstantial knowledge:
Detailed knowledge about: Safety precautions on maintaining the speed of D.C. machines.
Swali
What is the main purpose of installing a varistor in a DC machine field winding?