Mada za sehemu hiiErecting conduitsMada 2
- Erecting PVC conduits
- Erecting galvanized conduit
A galvanized conduit is a steel tube that has been coated with zinc to resist corrosion. It is used in electrical installations to protect wires and cables from physical damage, moisture, dust, and harsh weather conditions. This study note explains how to erect galvanized conduits correctly and safely.
A galvanized conduit is a type of metal conduit made from steel that has undergone galvanization — a process of coating the steel with zinc to prevent rusting and corrosion. This makes the conduit durable and suitable for environments where moisture or chemicals are present.
Galvanized conduits are available in two main types:
- Rigid galvanized conduits — straight, firm tubes that provide strong protection but cannot be bent manually.
- Flexible galvanized conduits — made by spirally winding a metal strip and coating it with a flexible PVC layer. These can be bent to navigate around obstacles.
Advantages
- High mechanical strength and durability
- Fire-resistant, providing extra safety in case of fire
- Resistant to corrosion when properly galvanized
- Suitable for harsh industrial environments
- Provides excellent protection against physical damage
Disadvantages
- More expensive than PVC conduits
- Heavier and more difficult to handle
- Can corrode if the galvanization is damaged
- Requires more effort to install compared to PVC
Galvanized conduits are used in:
- Industrial factories and manufacturing plants where strong protection is needed
- Commercial buildings requiring durable cable protection
- Areas exposed to high temperatures
- Underground installations where cables face mechanical stress
- Locations requiring extra fire resistance
When installing conduits, electricians must navigate around obstacles such as walls, beams, and corners. This is achieved by bending the conduit. The common types of bends include:
90° Stub-up bend
This is the most common bend, forming an L-shape at a 90° angle. It is used to run conduits up or down walls, through floors or ceilings, and around inner and outer corners.
25° Offset bend
This bend is formed by two consecutive 90° bends, creating an S-shape. It is used when a conduit needs to change direction twice in a tight space, such as running around a beam and then continuing along a wall.
Offset bend
This bend allows the conduit to navigate around obstacles by forming an S-shape. It is commonly used when a conduit needs to change elevation while avoiding objects.
Saddle bend
This bend allows the conduit to go over an obstacle and then return to its original path. It is used for crossing over existing conduits, beams, or pipes.
There are two main methods for bending conduits:
Cold bending
Cold bending is performed at room temperature without applying heat. It is commonly used for metal conduits like galvanized steel. The process uses a bending tool or machine to create smooth curves quickly. This method is faster and produces consistent results but requires proper tools.
Hot bending
Hot bending involves heating the conduit to make it flexible before bending. This method is mainly used for PVC conduits. For galvanized conduits, hot bending is generally not recommended because heat can damage the zinc coating and reduce corrosion resistance.
Important: When bending galvanized conduits, always use cold bending methods to preserve the zinc coating.
The space factor refers to the ratio of space occupied by cables inside the conduit to the total internal cross-sectional area of the conduit. According to standards (BS 7671 and IEC 60364), the space factor for conduits should not exceed 40%.
This means that cables must not fill more than 40% of the conduit's interior. This limit is important to:
- Prevent damage to cable insulation during pulling
- Reduce mechanical stress on cables
- Allow air circulation to prevent heat buildup
- Make future maintenance easier
Problem: An electrician needs to install three 2.5 mm² single-core cables inside a galvanized conduit. Each cable has a cross-sectional area of approximately 5 mm². The conduit has an internal cross-sectional area of 50 mm². Calculate the space factor and determine if it is within the acceptable limit.
Solution:
Total cable area = 3 × 5 mm² = 15 mm²
Space factor = (Total cable area ÷ Conduit internal area) × 100 = (15 ÷ 50) × 100 = 30%
Since 30% is less than 40%, this installation meets the space factor requirement.
The following tools and equipment are needed:
- Combination pliers
- Electrician knife
- Measuring tape
- Long nose pliers
- Claw hammer
- Set of screwdrivers
- Bench vice
- Bending block or bending machine
- Draw wire (snake wire)
- Round files
- Spirit level
- Chisel
- Chest drill machine
- Spring bender (for cold bending)
Before starting any conduit installation:
- Wear appropriate PPE: leather gloves, overalls, safety boots, and safety goggles
- Inspect the site for hazards such as flammable materials or unstable surfaces
- Ensure the power supply is switched off and locked out
- Check that conduit sizes are correct for the intended cables
- Route conduits away from other services like water pipes and communication cables
- Securely support and attach conduits at proper intervals
- Follow manufacturer guidelines and relevant standards for bending
- Keep the work area clean and organized
During installation:
- Use correct bending techniques to avoid kinking or damaging the conduit
- Ensure bends maintain the minimum bending radius to prevent cable damage
- Check that conduits are properly aligned using a spirit level
After installation:
- Perform a visual inspection to ensure everything is correctly in place
- Verify that supports and connections are secure
In Tanzania, galvanized conduits are commonly used in commercial buildings such as markets, schools, and small businesses in cities like Dar es Salaam and Arusha. For example, when an electrician wires a new kiosk at a local market, using galvanized conduits to protect the cables running along the walls ensures the installation lasts longer despite dust, moisture, and potential physical knocks from daily activities. This reduces maintenance costs and prevents electrical hazards for the shop owner.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Interpret architectural drawing.
- Draw electrical diagrams.
- Identify tools, equipment and materials required.
- Mark the conduit run.
- Cut/chase in the wall for conduits.
- Cut conduit for the required length.
- Make bends and corners.
- Mount the conduits and support them.
- Terminate conduits with required boxes.
- Clean work area.
- Store tools, equipment and safety gears.
Tathmini ya matokeo
Galvanized conduit system securely mounted as per procedures prescribed by the I.E.E. regulations.
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to erect galvanized conduit systems.
Principles: The student should explain the principles related to erecting galvanized conduit.
Theories: The student should explain:
- The application of metal conduit.
- The space factor of the conduit.
- Advantage and disadvantages of metal conduit wiring system over plastic conduit.
Detailed knowledge about:
- Safety precautions on choosing conduit size.
- I.E.E. regulations. Maintenance of buildings