Mada za sehemu hiiDesigning and making domestic freezersMada 6
- Designing and drawing working drawing of chest-freezer
- Making freezer body
- Making evaporator coil
- Constructing refrigerant pipe circuit
- Installing electrical wiring circuit
- Charging with refrigerant and commissioning the system
Charging Refrigerant and Commissioning the System
Charging refrigerant and commissioning the system are the final steps in assembling a domestic refrigerator or freezer. After the cabinet, compressor, condenser, evaporator, and piping have been installed, the system must be evacuated, charged with the correct refrigerant, and tested to ensure it operates efficiently and safely.
- Refrigerant – A substance that absorbs heat from the interior of a refrigerator and releases it outside, enabling cooling. Common refrigerants used in domestic systems include R-134a and R-600a (isobutane).
- Charging – The process of adding the correct amount of refrigerant into the sealed refrigeration system.
- Commissioning – The process of testing, adjusting, and verifying that the refrigeration system operates correctly after charging.
Before charging or commissioning, always observe these safety rules:
- Wear safety gloves, goggles, and protective clothing.
- Ensure good ventilation in the working area.
- Never overcharge the system – this causes high pressure and can damage the compressor.
- Keep open flames away from the working area, as refrigerants can produce toxic gases when heated.
- Use leak detectors to check for refrigerant leaks after charging.
1. Evacuate the System
Before charging, the system must be evacuated to remove air and moisture:
- Connect the manifold gauge to the service ports (high-side and low-side).
- Connect the vacuum pump to the manifold gauge.
- Open both valves on the manifold gauge and run the vacuum pump for at least 30 minutes.
- Close the valves and check that the gauge maintains a vacuum – this confirms the system is leak-free.
2. Connect the Refrigerant Cylinder
- Connect the refrigerant cylinder to the manifold gauge's center port.
- For R-134a systems, place the cylinder upright; for R-600a (flammable), keep it upright and ensure proper ventilation.
3. Charge the Correct Amount
- The correct charge amount is specified by the refrigerator manufacturer and is usually marked on the rating plate.
- Open the refrigerant cylinder valve and the low-side valve on the manifold gauge to allow refrigerant to enter the system.
- Monitor the manifold gauge:
- Low-side pressure should read approximately 0.5–1.0 bar (7–15 psi) at ambient temperature.
- High-side pressure should rise to 7–10 bar (100–145 psi) once the compressor runs.
4. Check for Leaks
- Use an electronic leak detector or soap bubble solution around all joints and connections.
- If bubbles appear, tighten the connection or repair the leak, then re-check.
After charging, the system must be tested and adjusted:
- Start the compressor – Turn on the refrigerator and listen for smooth operation.
- Measure temperatures – Place a thermometer in the fresh food compartment (should reach 0–5°C) and in the freezer compartment (should reach -18°C or lower).
- Check compressor amperage – Use a multimeter to verify the compressor draws the current specified on the nameplate.
- Verify airflow – Ensure air circulates freely around the condenser coils at the back of the unit.
- Observe cycling – The compressor should cycle on and off automatically as the thermostat demands cooling.
- Record measurements – Document all pressures, temperatures, and current readings for future reference.
| Tool | Purpose |
|---|---|
| Manifold gauge | Measures high-side and low-side pressures |
| Vacuum pump | Removes air and moisture from the system |
| Leak detector | Identifies refrigerant leaks |
| Multimeter | Measures electrical current and voltage |
| Thermometer | Measures compartment temperatures |
| Megger | Tests insulation resistance of the compressor |
A domestic refrigerator uses R-134a refrigerant. The manufacturer's nameplate specifies a charge of 120 grams. During commissioning at an ambient temperature of 25°C, the technician records the following readings:
- Low-side pressure: 0.8 bar
- High-side pressure: 8.5 bar
- Fresh food compartment: 4°C
- Freezer compartment: -19°C
Verification: Are the readings correct?
- Low-side pressure of 0.8 bar at 25°C is within the normal range (0.5–1.0 bar).
- High-side pressure of 8.5 bar is within the normal range (7–10 bar).
- Temperatures meet the required standards (0–5°C for fresh food, -18°C or below for freezer).
Conclusion: The system is properly charged and commissioned.
- Always evacuate the system before charging to remove air and moisture.
- Charge only the exact amount of refrigerant specified by the manufacturer.
- Use manifold gauges to monitor pressures during charging.
- Commission the system by checking temperatures, pressures, and electrical readings.
- Perform a leak test after charging and document all measurements.
In Tanzania, domestic refrigerators are essential for preserving food in households and small shops (duka la mboga). A technician who correctly charges and commissions a refrigerator ensures that food such as fish, vegetables, and milk stays fresh longer, reducing waste and helping families save money. Proper commissioning also extends the lifespan of the appliance, which is important for small business owners who rely on refrigeration to sell perishable goods in local markets.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
The student should be able to:
- Select materials, tools and equipment
- Mount the refrigerating components
- Pipe the refrigerating components
- Mount electrical and perform wiring of the circuit
- Perform finishing to aesthetic appearance
- Charge the systems with refrigerant (R134a)
- Apply safety measures
- Commission the performance
- Clean the workplace, tools and equipment
- Store tools, equipment and machine
Tathmini ya matokeo
Designed and made freezer conform to technical specifications and aesthetic appearance
Tathmini ya maarifa
Knowledge Evidence:
Detailed knowledge of:
Method used: The student should explain how to:
- Select the appropriate refrigerant to charge the freezers
- Charge the Freezer
Principles: The student should explain the principles of: (q) Heat transfer and exchange (r) Design parameters
Theories: The student should explain:
- Steps to estimate refrigerating capacity of a unit
- Materials science
Circumstantial knowledge:
Detailed knowledge about:
- Safe handling of tools, equipment and machines
- Environmental regulations
Swali
What is the first step that must be performed before charging refrigerant into a refrigeration system?