Mada za sehemu hiiServicing compressor above 60 kWMada 7
- Dismantling for overhaul and assembling
- Lubricating bearing
- Replacing bearing
- Replacing oil seal
- Replacing piston rings
- Replacing valves
- Measuring electrical quantities
Understanding Dismantling of Compressors for Overhaul
Dismantling is the systematic process of carefully taking apart a refrigeration or air conditioning compressor to inspect, clean, repair, or replace worn-out components. When servicing compressors above 60 kW (kilowatts), proper dismantling is essential for effective overhaul and reassembly, ensuring the system operates efficiently and safely.
The main purposes of dismantling a compressor are:
- Inspection – To examine internal components for wear, damage, or corrosion
- Cleaning – To remove dirt, oil residue, and contaminants from parts
- Repair or Replacement – To fix faulty components such as valves, pistons, bearings, or seals
- Overhaul – To restore the compressor to good working condition
- Reassembly – To put the compressor back together correctly after servicing
Before starting any dismantling work, always follow these safety rules:
- Disconnect power – Ensure the compressor is completely disconnected from the electrical supply
- Release refrigerant – Use proper procedures to recover the refrigerant according to environmental regulations
- Release pressure – Bleed all pressure from the system using the service valves
- Allow cooling – Let the compressor cool down to avoid burns from hot components
- Wear protective gear – Use gloves, safety goggles, and dust masks as required
- Secure the work area – Keep the area clean and free from obstacles
The following tools and equipment are needed for dismantling compressors:
- Working hand gloves
- Electro-mechanical toolbox (screwdrivers, wrenches, pliers)
- Wire brush and revolving wire brush
- Lifting tackles (for heavy components)
- Grease gun
- Compressed air hose with supply
- Refrigerant leak detector
- Flashlight and inspection lamp
- Pail or containers (for small parts and oil)
- Dust mask
Step 1: Preparation and Initial Inspection
- Review the manufacturer's service manual for the specific compressor model
- Identify all fasteners, gaskets, and connection points
- Photograph the compressor before dismantling for reference during reassembly
- Label all wires, pipes, and connections
Step 2: Removing External Components
- Disconnect electrical connections and remove the motor cover
- Remove bolts securing the compressor housing or crankcase
- Carefully detach suction and discharge pipes
- Remove oil drain plugs and collect the oil in a clean container
Step 3: Opening the Compressor Housing
- Use appropriate lifting tackles for heavy components
- Remove the cylinder head or end cover carefully
- Inspect the gasket surfaces for damage
- Keep all bolts, nuts, and small parts organized in containers
Step 4: Removing Internal Components
- Piston assemblies – Carefully remove pistons, connecting rods, and wrist pins
- Valve plates – Remove suction and discharge valve assemblies
- Bearings – Extract bearing covers and bearings using proper tools
- Shaft seal – Remove the mechanical seal if equipped
- Use wire brushes to clean components without damaging surfaces
Step 5: Cleaning and Inspection
- Clean all parts with approved cleaning agents
- Use compressed air to blow out passages and cavities
- Inspect each component for wear, cracks, or damage
- Measure clearances and compare with manufacturer specifications
- Replace worn or damaged parts with genuine spares
Step 6: Organizing Parts for Reassembly
- Arrange parts in the order they will be reinstalled
- Store small parts in labelled containers
- Apply grease to bearings and moving parts as specified
- Prepare new gaskets and seals for reassembly
- Always work in a clean, well-lit area to prevent contamination
- Use proper lifting techniques to avoid injury when handling heavy components
- Never force stuck bolts – apply penetrating oil and allow time before retrying
- Keep all parts organized to simplify reassembly
- Follow the reverse order of dismantling when reassembling
- Torque all fasteners to the manufacturer's specified values
After completing the dismantling process, verify that:
- All components have been inspected and measured
- Damaged parts have been identified for replacement
- Cleaning has been completed thoroughly
- Parts are properly organized for reassembly
- Documentation and photographs are available for reference
In Tanzania, technicians working on large air conditioning systems in hotels, hospitals, or industrial buildings along Morogoro Road or in Dar es Salaam must regularly service compressors above 60 kW. For example, a refrigeration technician at a fish processing plant in Mwanza may need to dismantle a large reciprocating compressor to replace worn valve plates, ensuring the cold storage facility keeps fish fresh for market. This skill enables technicians to extend equipment life, reduce repair costs for small businesses, and maintain food safety standards across Tanzania's fishing and food supply chains.
Jinsi utakavyotathminiwaTathmini ya mchakato · Tathmini ya matokeo · Tathmini ya maarifa
Tathmini ya mchakato
- Select tools and equipment for a task
- Performing diagnostic troubleshooting
- Performing bearing greasing
- Performing pump down
- Replace air filters
- Repair compressors
- Detect leaks
- Performing sheet metal works
- Inspect electrical components
- Carry out plumbing works
- Check/refill oil level
- Store tools and equipment
- Clean equipment and workplace
Tathmini ya matokeo
A record of service works carried out conforms to technical specifications
Tathmini ya maarifa
Knowledge evidence:
Detailed knowledge of:
Method used: The student should explain how to:
- Assemble and disassemble according to procedures
- Apply different leakage detection methods
- Performing diagnostic trouble shooting
Principles: The student should explain the principles of:
- Heat transfer in a heat exchanger
- Compression refrigeration cycle
- Primary and secondary refrigerants
Theories: The student should explain:
- Pressure temperature charts for different refrigerants
- Super heating as it refers to refrigeration
- Application of oil and greasing lubricants
Detailed knowledge about:
- Safe handling of working tools and equipment
- Electric circuitry
- Pressure and temperature quantities with reference to refrigeration
- Safe handling of refrigerants during charging, discharging and storage Environmental regulations on green gases
Swali
What is one of the main purposes of dismantling a refrigeration compressor for servicing?